SCM203
Industrial signal conditioner
SCM203
Industrial signal conditioner
FEATURES
- Galvanic isolation of input and output current loop
- Power supplied from current loops
- Monitoring current loop without interrupting it
- Input and Output overvoltage protection
- Input and Output overcurrent protection
- High linearity and temperature stability
- Short response time
- Low output ripple
- 35mm DIN rail mounting
DESCRIPTION
SCM 203 is a current isolator intended for mounting on DIN 35mm rail. It provides galvanic isolation of current sensing loops. Conversion is linear. Connecting of input (4-20mA) and output (4-20mA) current is two way and passive which means that converter is power supplied from current loops. By connecting voltmeter to test connectors it is possible to monitor loop current without interrupting it.
APPLICATION
Analog signal conditioners convert, isolate, and amplify signals. SCM203 can convert 4 to 20 mA current signals to standard 4 to 20 mA signals. Also, it can isolate multiple field-measurement devices on a common power supply to help prevent interference that can occur due to ground loops or common-mode noise.
TECHNICAL SPECIFICATION
Accuracy | ±0.1% typical of full range |
Temperature stability | ±0.02%/oC
|
Response time | 220 ms (0-98%)
|
Output voltage ripple | 0.1% of full range RMS
|
Upper cut-off frequency (-3dB) | 3kHz |
Galvanic isolation | 5.3 KV RMS in 1sec
|
Voltage power supply of the loop | 10-32VDCc
|
Output current | 4-20mA
|
Test connection | 40-200mV represents 4-20mA (shunt 10ohm ±1%)
|
Output over-voltage protection | 33V tranzorb
|
Output over-current protection | fuse slow 125mA 20x5mm
|
Loop resistance | Rmax(ohms)=(Vsupply-10)/0.02
|
Input current | 4-20mA/32V max
|
Input overvoltage protection | 33V transzorb
|
Input overcurrent protection | fuse slow 125mA 20x5mm
|
Temperature range | 0-70 oC non condensed
|
Case | plastic case 35x90x70mm, IP50
|
Mounting | DIN 35mm rail |